horizontalSpanLengthLength (m / ft)
The horizontal chord distance L between transmission structures, measured orthogonally to gravity. For utility distribution and EHV transmission lines, standard spans range between 50 m and 1,200 m (160 ft to 4,000 ft). In long-span river, valley, or fjord crossings exceeding 1,500 m, catenary formulations must strictly replace parabolic approximations to prevent ground clearance violations under high-temperature IEEE 738 thermal ratings.
Default: 300 m (984.25 ft)
elevationDifferentialHeight Offset (m / ft)
The vertical height difference h = h₂ - h₁ between the higher and lower cable suspension attachment points. Non-zero values shift the catenary vertex nadir xm away from midspan toward the lower support. When h > 2c · sinh(L / 2c), xm becomes negative, creating a virtual low point where the conductor exerts continuous vertical uplift (negative reaction force) on the lower structure crossarm.
Default: 15 m (49.21 ft)
horizontalTensionForce (kN / lbf)
The horizontal component H of cable axial tension, invariant across the entire span profile under static equilibrium. Governed by NESC Rule 252 and IEC 60826 structural limits: initial unloaded tension must not exceed 35% of the Rated Tensile Strength (RTS) at 60°F (15°C), final unloaded tension must remain below 25% RTS to mitigate Aeolian fatigue, and combined extreme ice/wind loading must not exceed 50% to 60% RTS.
Default: 25.0 kN (5,620 lbf)
bareConductorWeightLinear Mass Density (kg/m / lb/ft)
The bare linear unit weight w_bare of the stranded conductor or messenger wire (e.g., standard 795 kcmil 26/7 ACSR 'Drake' at 1.628 kg/m or 1.094 lb/ft; 477 kcmil 'Hawk' at 0.976 kg/m or 0.656 lb/ft). In overhead catenary systems, this gravitational deadload vector acts purely along the true arc length ds rather than horizontal projection dx.
Default: 1.628 kg/m (1.094 lb/ft)
radialIceThicknessRadial Coating (mm / in)
Uniform radial glaze ice accretion t_ice adhering around the circumference of the cable sheath. Calibrated to NESC Table 250-1 districts: Light (0.00 in / 0 mm), Medium (0.25 in / 6.35 mm at 15°F), and Heavy (0.50 in / 12.7 mm at 0°F), with rime ice density standardized at 913 kg/m³ (57 lb/ft³). The total augmented cable cross-section dramatically scales total deadload and effective wind drag projection.
Default: 12.7 mm (0.50 in)
transverseWindPressureAerodynamic Pressure (Pa / lb/ft²)
Dynamic wind pressure P_w acting transversely across the projected ice-jacketed conductor diameter D_tot = d_cable + 2·t_ice. Standard NESC design benchmarks apply 192 Pa (4.0 lb/ft²) in Heavy/Medium zones and 431 Pa (9.0 lb/ft²) in Light zones, derived from gust kinetic pressure ½·ρ_air·V²·C_d with conductor aerodynamic drag coefficient C_d typically parameterized between 1.0 and 1.2 under ASCE Manual 74.
Default: 192 Pa (4.0 lb/ft²)